DocumentCode :
761308
Title :
Split-conductor current sensors with electronic load termination
Author :
Milkovic, Miran
Author_Institution :
Sch. of Electr. Eng., Georgia Inst. of Technol., Atlanta, GA, USA
Volume :
41
Issue :
4
fYear :
1992
fDate :
8/1/1992 12:00:00 AM
Firstpage :
540
Lastpage :
547
Abstract :
Split-conductor current sensors for measurement of 60 Hz alternating currents have electronic load termination to improve the sensor´s linearity. AC currents from 0.1 A to 300 A, with a magnitude error of 0.2-2% of reading at fundamental frequency, and a phase error of 0.1°-2° of -25°C to +75°C. H-compensated current sensors have shown a magnitude error of 0.1% of point and a phase error of 6 min of point in a 150/1 current dynamic range. Current ratios of more than 50000:1 have been achieved. Sensor power dissipation was less than 1 W at 100 A
Keywords :
electric current measurement; electric sensing devices; -25 to 75 degC; 0.1 to 300 A; 60 Hz; AC currents; H-compensated current sensors; electric sensor; electronic load termination; phase error; power dissipation; split conductor current sensor; Circuits; Current measurement; Current transformers; Dynamic range; Ferrites; Frequency; Linearity; Power dissipation; Power measurement; Transformer cores;
fLanguage :
English
Journal_Title :
Instrumentation and Measurement, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9456
Type :
jour
DOI :
10.1109/19.155922