• DocumentCode
    772405
  • Title

    Transient overvoltages and overcurrents on 12.47 kV distribution lines: Field test results

  • Author

    Kolcio, N. ; Halladay, J.A. ; Allen, G.D. ; Fromholtz, E.N.

  • Author_Institution
    American Electric Power Service Corp., Columbus, OH, USA
  • Volume
    7
  • Issue
    3
  • fYear
    1992
  • fDate
    7/1/1992 12:00:00 AM
  • Firstpage
    1359
  • Lastpage
    1370
  • Abstract
    The authors report on field tests conducted by American Electric Power (AEP) on a 12.47 kV distribution line. The results cover capacitor switching and load dropping tests. The highest overvoltage recorded of 2.43 p.u. was during capacitor switching with arresters disconnected. At the line end, a maximum of 2.16 p.u. was measured during the line reenergization with the capacitor bank disconnected. The results give both overvoltage and overcurrent transient waveshape, magnitude, and dominant frequency. Spectrum analysis of selected test shots provided information on the extent of transient nonlinearity. Information is given on the field test instrumentation setup
  • Keywords
    distribution networks; overcurrent; overvoltage; power cables; testing; transients; 12.47 kV; AEP; American Electric Power; capacitor switching; distribution lines; dominant frequency; field tests; instrumentation setup; load dropping; spectrum analysis; transient nonlinearity; transient overcurrents; transient overvoltages; transient waveshape; Arresters; Capacitors; Circuit testing; Frequency; Power system transients; Senior members; Stress; Surges; Switching circuits; Transformers;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.141853
  • Filename
    141853