Title :
Transient overvoltages and overcurrents on 12.47 kV distribution lines: Field test results
Author :
Kolcio, N. ; Halladay, J.A. ; Allen, G.D. ; Fromholtz, E.N.
Author_Institution :
American Electric Power Service Corp., Columbus, OH, USA
fDate :
7/1/1992 12:00:00 AM
Abstract :
The authors report on field tests conducted by American Electric Power (AEP) on a 12.47 kV distribution line. The results cover capacitor switching and load dropping tests. The highest overvoltage recorded of 2.43 p.u. was during capacitor switching with arresters disconnected. At the line end, a maximum of 2.16 p.u. was measured during the line reenergization with the capacitor bank disconnected. The results give both overvoltage and overcurrent transient waveshape, magnitude, and dominant frequency. Spectrum analysis of selected test shots provided information on the extent of transient nonlinearity. Information is given on the field test instrumentation setup
Keywords :
distribution networks; overcurrent; overvoltage; power cables; testing; transients; 12.47 kV; AEP; American Electric Power; capacitor switching; distribution lines; dominant frequency; field tests; instrumentation setup; load dropping; spectrum analysis; transient nonlinearity; transient overcurrents; transient overvoltages; transient waveshape; Arresters; Capacitors; Circuit testing; Frequency; Power system transients; Senior members; Stress; Surges; Switching circuits; Transformers;
Journal_Title :
Power Delivery, IEEE Transactions on