DocumentCode :
772405
Title :
Transient overvoltages and overcurrents on 12.47 kV distribution lines: Field test results
Author :
Kolcio, N. ; Halladay, J.A. ; Allen, G.D. ; Fromholtz, E.N.
Author_Institution :
American Electric Power Service Corp., Columbus, OH, USA
Volume :
7
Issue :
3
fYear :
1992
fDate :
7/1/1992 12:00:00 AM
Firstpage :
1359
Lastpage :
1370
Abstract :
The authors report on field tests conducted by American Electric Power (AEP) on a 12.47 kV distribution line. The results cover capacitor switching and load dropping tests. The highest overvoltage recorded of 2.43 p.u. was during capacitor switching with arresters disconnected. At the line end, a maximum of 2.16 p.u. was measured during the line reenergization with the capacitor bank disconnected. The results give both overvoltage and overcurrent transient waveshape, magnitude, and dominant frequency. Spectrum analysis of selected test shots provided information on the extent of transient nonlinearity. Information is given on the field test instrumentation setup
Keywords :
distribution networks; overcurrent; overvoltage; power cables; testing; transients; 12.47 kV; AEP; American Electric Power; capacitor switching; distribution lines; dominant frequency; field tests; instrumentation setup; load dropping; spectrum analysis; transient nonlinearity; transient overcurrents; transient overvoltages; transient waveshape; Arresters; Capacitors; Circuit testing; Frequency; Power system transients; Senior members; Stress; Surges; Switching circuits; Transformers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.141853
Filename :
141853
Link To Document :