DocumentCode
772405
Title
Transient overvoltages and overcurrents on 12.47 kV distribution lines: Field test results
Author
Kolcio, N. ; Halladay, J.A. ; Allen, G.D. ; Fromholtz, E.N.
Author_Institution
American Electric Power Service Corp., Columbus, OH, USA
Volume
7
Issue
3
fYear
1992
fDate
7/1/1992 12:00:00 AM
Firstpage
1359
Lastpage
1370
Abstract
The authors report on field tests conducted by American Electric Power (AEP) on a 12.47 kV distribution line. The results cover capacitor switching and load dropping tests. The highest overvoltage recorded of 2.43 p.u. was during capacitor switching with arresters disconnected. At the line end, a maximum of 2.16 p.u. was measured during the line reenergization with the capacitor bank disconnected. The results give both overvoltage and overcurrent transient waveshape, magnitude, and dominant frequency. Spectrum analysis of selected test shots provided information on the extent of transient nonlinearity. Information is given on the field test instrumentation setup
Keywords
distribution networks; overcurrent; overvoltage; power cables; testing; transients; 12.47 kV; AEP; American Electric Power; capacitor switching; distribution lines; dominant frequency; field tests; instrumentation setup; load dropping; spectrum analysis; transient nonlinearity; transient overcurrents; transient overvoltages; transient waveshape; Arresters; Capacitors; Circuit testing; Frequency; Power system transients; Senior members; Stress; Surges; Switching circuits; Transformers;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.141853
Filename
141853
Link To Document