• DocumentCode
    772544
  • Title

    Continuous regulation of capacitive reactive power

  • Author

    Karady, George G.

  • Author_Institution
    Arizona State Univ., Tempe, AZ, USA
  • Volume
    7
  • Issue
    3
  • fYear
    1992
  • fDate
    7/1/1992 12:00:00 AM
  • Firstpage
    1466
  • Lastpage
    1473
  • Abstract
    A novel method for the continuous regulation of reactive power generated by a capacitor bank is presented. The two proposed control circuits consist of capacitor banks controlled by bidirectional switches which are built with antiparallel connected thyristor and GTO (gate turn-off thyristor) valves, or with two GTO valves. The current of the capacitor is regulated by turning off the GTO switch before zero current crossing. By tuning off the current, charge is trapped in the capacitor, resulting in a constant capacitor voltage. To avoid the current surge, the switch is turned on when the supply and capacitor voltage are equal. The current regulation is achieved by switching off the current for a part of each cycle. The feasibility of the method has been verified by extensive transient analysis. The advantage of the proposed system is the fast and continuous regulation of reactive power without inductance
  • Keywords
    capacitor storage; power control; reactive power; thyristor applications; GTO valves; antiparallel connected thyristor; bidirectional switches; capacitor bank; capacitor voltage; extensive transient analysis; gate turn-off thyristor; reactive power continuous regulation; zero current crossing; Circuit optimization; Power generation; Reactive power; Switched capacitor circuits; Switches; Switching circuits; Thyristors; Turning; Valves; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.141866
  • Filename