DocumentCode :
772558
Title :
Correlation of AC, switching surge and DC breakdown test results for insulating blankets and line hoses
Volume :
7
Issue :
3
fYear :
1992
fDate :
7/1/1992 12:00:00 AM
Firstpage :
1474
Lastpage :
1483
Abstract :
Information reported during the ESMO-90 panel session, entitled Rationale for Test Criteria of Live-Line Maintenance Protective Equipment is presented. The rationale for electrical testing of live line maintenance tools, in particular, the insulating protective equipment (IPE), such as insulating blankets and line hoses, is discussed. The present status of such testing is compared to the existing standards. The main thrust is the presentation of test results from a special international test program involving ten laboratories. Data are given on the breakdown voltage correlation between power frequency, direct current, and switching overvoltage tests. The results indicate that the equivalence in testing between power frequency and DC, and power frequency and switching overvoltage now used in the industry and standards may be incorrect
Keywords :
maintenance engineering; overvoltage; safety; standards; testing; AC tests; DC breakdown tests; breakdown voltage correlation; insulating blankets; insulating protective equipment; international test program; line hoses; live line maintenance tools; power frequency; safety; standards; switching overvoltage tests; Dielectrics and electrical insulation; Electric breakdown; Frequency; Hoses; Information analysis; Laboratories; Safety devices; Surge protection; Testing; Voltage control;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.141867
Filename :
141867
Link To Document :
بازگشت