DocumentCode :
772596
Title :
Critical switching impulse strength of long air gaps: modelling of air density effects
Author :
Rizk, Farouk A.M.
Author_Institution :
Inst. de Recherche d´´Hydro-Quebec, Varennes, Que., Canada
Volume :
7
Issue :
3
fYear :
1992
fDate :
7/1/1992 12:00:00 AM
Firstpage :
1507
Lastpage :
1515
Abstract :
A physical modeling approach to investigate the effect of reduced air density on leader inception and sparkover of long air gaps under positive switching impulses with critical front time is presented. The model accounts for the effect of air density on continuous leader inception voltage, leader length, and sparkover voltage. The results of the model provides critical positive switching impulse air density correction factors for rod-plane, rod-rod, conductor-plane, conductor-rod, and conductor-tower window gaps over a wide range of gap distances and relative air densities. The model findings were extensively checked against previous experimental results with quite satisfactory agreement
Keywords :
flashover; switching; air density effects; conductor-plane gaps; conductor-rod gaps; conductor-tower window gaps; continuous leader inception voltage; critical front time; leader inception; leader length; long air gaps; positive switching impulses; rod-plane gaps; rod-rod gaps; sparkover; sparkover voltage; Air gaps; Electric breakdown; Frequency; Humidity; IEC standards; Impulse testing; Insulation; Laboratories; Lightning; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.141871
Filename :
141871
Link To Document :
بازگشت