• DocumentCode
    772596
  • Title

    Critical switching impulse strength of long air gaps: modelling of air density effects

  • Author

    Rizk, Farouk A.M.

  • Author_Institution
    Inst. de Recherche d´´Hydro-Quebec, Varennes, Que., Canada
  • Volume
    7
  • Issue
    3
  • fYear
    1992
  • fDate
    7/1/1992 12:00:00 AM
  • Firstpage
    1507
  • Lastpage
    1515
  • Abstract
    A physical modeling approach to investigate the effect of reduced air density on leader inception and sparkover of long air gaps under positive switching impulses with critical front time is presented. The model accounts for the effect of air density on continuous leader inception voltage, leader length, and sparkover voltage. The results of the model provides critical positive switching impulse air density correction factors for rod-plane, rod-rod, conductor-plane, conductor-rod, and conductor-tower window gaps over a wide range of gap distances and relative air densities. The model findings were extensively checked against previous experimental results with quite satisfactory agreement
  • Keywords
    flashover; switching; air density effects; conductor-plane gaps; conductor-rod gaps; conductor-tower window gaps; continuous leader inception voltage; critical front time; leader inception; leader length; long air gaps; positive switching impulses; rod-plane gaps; rod-rod gaps; sparkover; sparkover voltage; Air gaps; Electric breakdown; Frequency; Humidity; IEC standards; Impulse testing; Insulation; Laboratories; Lightning; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.141871
  • Filename