DocumentCode
772719
Title
Insulation coordination, environmental and system analysis of existing double circuit line reconfigured to six-phase operation
Author
Stewart, J.R. ; Oppel, Laurie J. ; Thomann, Gary C. ; Dorazio, Thomas F. ; Brown, Matthew T.
Author_Institution
Power Technologies Inc., Schenectady, NY, USA
Volume
7
Issue
3
fYear
1992
fDate
7/1/1992 12:00:00 AM
Firstpage
1628
Lastpage
1633
Abstract
Conversion of an existing double-circuit 115 kV overhead transmission line near Binghamton, New York to six-phase operation will provide a commercial demonstration of feasibility of high phase order power transmission. Analyses of insulation performance, corona and field effects, and a load flow and system stability have been performed as part of the preliminary engineering for this project. It is shown that conversion of the Goudey-Oakdale double-circuit 115 kV line to 93 kV six-phase is possible if insulator strings are lengthened to 8 units/string. This results in a 40% increase in thermal loading capacity and a doubling of surge impedance loading, while meeting all applicable electrical environmental requirements
Keywords
corona; insulation co-ordination; load flow; power transmission lines; 115 kV; 93 kV; Binghamton; Goudey-Oakdale double-circuit; New York; corona; double circuit line; environmental analysis; high phase order power transmission; load flow; six-phase operation; surge impedance loading; system analysis; thermal loading capacity; transmission line; Corona; Insulation; Load flow; Load flow analysis; Performance analysis; Power engineering and energy; Power transmission; Power transmission lines; Stability analysis; Thermal loading;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.141883
Filename
141883
Link To Document