Abstract :
The fault resistance introduces an error in the fault distance estimate, and hence may create an unreliable operation of a distance relay. A new compensation method based on fault resistance calculation is presented. The fault resistance calculation is based on monitoring the active power at the relay point. The compensated fault impedance measures accurately the impedance between the relay location and the fault point. The relay has shown satisfactory performances under various fault conditions especially for the ground faults with high fault resistance. This new compensation method avoids the under-reach problem in ground distance relays
Keywords :
fault location; power transmission faults; power transmission protection; relay protection; active power monitoring; fault distance estimate; fault impedance compensation; fault resistance calculation; ground distance relay compensation; ground faults; Conductors; Electric resistance; Electrical resistance measurement; Impedance measurement; Power transmission lines; Protection; Protective relaying; Relays; Transmission line measurements; Voltage; Active power; distance protection; fault resistance; impedance measurement;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2006.874621
Filename :
1705538
Link To Document :
بازگشت