DocumentCode :
775030
Title :
An adaptive distance relay based on transient error estimation of CVT
Author :
He, Benteng ; Li, Yiquan ; Bo, Zhiqian Q.
Author_Institution :
Electr. Eng. Coll., Zhejiang Univ., Hangzhou
Volume :
21
Issue :
4
fYear :
2006
Firstpage :
1856
Lastpage :
1861
Abstract :
Simple delay solutions are usually used to prevent transient overreach caused by the transient error of a capacitor voltage transformer (CVT), which is very harmful to the safety and stability of operation of the power system. A proposed real-time CVT transient error estimation approach based on the chosen fundamental wave algorithm and the rated CVT parameters consists of two stages. The first stage obtains the error coefficient. The second stage estimates the measured error of the voltage amplitude according to the secondary side voltage. A novel adaptive distance relay approach is proposed, which can adjust operating thresholds according to the error. The approach hardly affects the performance for lines of normal length and operates rapidly for short lines with close-in faults, which is verified by the simulation studies. The overall performance is improved greatly in comparison with the general approach for distance relays
Keywords :
potential transformers; power system faults; power system protection; power system transients; relay protection; adaptive distance relay; capacitor voltage transformer; power system safety; power system stability; transient error estimation; transient overreach prevention; Capacitors; Delay; Error analysis; Power system measurements; Power system relaying; Power system stability; Power system transients; Protective relaying; Safety; Voltage transformers; Adaptive reactance relay; error estimation; relay protection; transient error of capacitor voltage transformer (CVT);
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2006.877098
Filename :
1705541
Link To Document :