    Comparison of sensitivity between UHF method and IEC 60270 for onsite calibration in various GIS

  • Author

    Hoshino, Toshihiro ; Koyama, Hiroshi ; Maruyama, Shiro ; Hanai, Masahiro

  • Author_Institution
    Toshiba Corp., Kanagawa
  • Volume
    21
  • Issue
    4
  • fYear
    2006
  • Firstpage
    1948
  • Lastpage
    1953
  • Abstract
    It is more important to obtain the sensitivity line, which is defined as a correlation between the ultra-high-frequency (UHF) signal (mV) and apparent charge (pC), for onsite calibration regarding partial discharge (PD). Synchronous measurement of the UHF method and IEC 60270 enables us to obtain the sensitivity line and to estimate the apparent charge in on-site substations. The sensitivity line of 3-phase gas-insulated switchgear (GIS) is compared to that of single-phase GIS, and differences in defects are also discussed. The fundamental data in this paper contribute to on-site insulation diagnosis of GIS
  • Keywords
    calibration; gas insulated switchgear; partial discharges; GIS; IEC 60270; UHF method; apparent charge; gas-insulated switchgear; onsite calibration; onsite substations; partial discharge; synchronous measurement; ultrahigh frequency signal; Calibration; Charge measurement; Current measurement; Geographic Information Systems; IEC standards; Partial discharge measurement; Partial discharges; Substations; Switchgear; UHF measurements; Calibration; IEC 60270; gas-insulated switchgear (GIS); insulation diagnosis; partial discharge; ultra-high-frequency (UHF) method;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2006.874655
  • Filename
    1705554