Abstract
A new method for locating faults in two-terminal transmission lines is discussed. The procedure is based on the fundamental components of fault and prefault voltage at 50/60 Hz measured at the two ends of a transmission line. The methodology allows one to establish a direct calculation procedure that is independent of fault and prefault currents, fault type, fault resistance, synchronisation condition of register devices located on line ends, and prefault condition, either balanced or not. This is achieved by defining a new concept called `distance factor´. The technique developed was validated at two levels: first, from exact data obtained using a fault simulation software program, which allows the accuracy to be evaluated, and secondly, from erroneous voltage data taken at the ends of the line or from erroneous source impedances, which allows assessment of the sensitivity against incorrect data
Keywords
electric impedance; fault location; power transmission lines; sensitivity analysis; 50 Hz; 60 Hz; distance factor; erroneous source impedances; erroneous voltage data; fault location; fault simulation software program; fault voltage; prefault voltage; sensitivity assessment; transmission line; two-terminal transmission lines;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:19960112
Filename
488053
Link To Document