Abstract
The paper describes a new technique for protecting EHV teed transmission lines that is based on nonunit principles but exhibits the properties of a unit protection scheme. Fault generated (HF) signals are extracted by coupling a capacitor of a conventional capacitor voltage transformer (CVT) with a specially designed measurement circuit. Power line carrier line traps are used to confine the HF signals to the protected zone and their bandstop characteristics are used as a basis for discriminating between internal and external faults. A digital signal processing unit is used to process the signals and produce a trip output. Some simulated results are presented to show the ability of the scheme to rapidly detect faults on different teed circuits under a variety of system and fault conditions encountered in practice
Keywords
carrier transmission on power lines; fault diagnosis; potential transformers; power system CAD; power system protection; signal detection; EHV teed circuits; bandstop characteristics; capacitor voltage transformer; computer-aided design; digital signal processing unit; fault generated (HF) signals; measurement circuit; nonunit protection scheme; power line carrier line traps; signal detection;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:19960052
Filename
488149
Link To Document