• DocumentCode
    776059
  • Title

    Computer-aided design of a new nonunit protection scheme for EHV teed circuits

  • Author

    Carter, A.M. ; Aggarwal, R.K. ; Johns, A.T. ; Bo, Z.Q.

  • Author_Institution
    Sch. of Electron. & Electr. Eng., Bath Univ., UK
  • Volume
    143
  • Issue
    2
  • fYear
    1996
  • fDate
    3/1/1996 12:00:00 AM
  • Firstpage
    142
  • Lastpage
    150
  • Abstract
    The paper describes a new technique for protecting EHV teed transmission lines that is based on nonunit principles but exhibits the properties of a unit protection scheme. Fault generated (HF) signals are extracted by coupling a capacitor of a conventional capacitor voltage transformer (CVT) with a specially designed measurement circuit. Power line carrier line traps are used to confine the HF signals to the protected zone and their bandstop characteristics are used as a basis for discriminating between internal and external faults. A digital signal processing unit is used to process the signals and produce a trip output. Some simulated results are presented to show the ability of the scheme to rapidly detect faults on different teed circuits under a variety of system and fault conditions encountered in practice
  • Keywords
    carrier transmission on power lines; fault diagnosis; potential transformers; power system CAD; power system protection; signal detection; EHV teed circuits; bandstop characteristics; capacitor voltage transformer; computer-aided design; digital signal processing unit; fault generated (HF) signals; measurement circuit; nonunit protection scheme; power line carrier line traps; signal detection;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:19960052
  • Filename