DocumentCode
776182
Title
Partial discharge activity in gas-insulated system under composite voltage
Author
Sarathi, R. ; Dubey, Vishal ; Srinivasa, Y.G.
Author_Institution
Dept. of Electr. Eng., Indian Inst. of Technol. Madras, Chennai, India
Volume
21
Issue
1
fYear
2006
Firstpage
499
Lastpage
500
Abstract
In the present study, the partial-discharge activity under nonstandard voltage formed by ac and dc voltages was studied. It is identified that the ac superposed with positive dc enhances the discharge activity in the medium and if the ac voltage is superposed with the negative dc, it can mitigate the discharge activity. The acoustic emission signal generated due to the partial discharges in gas-insulated systems under the composite voltage formed by ac superposed with dc voltage/ac/dc voltages, has a dominant frequency content at around 250 kHz.
Keywords
SF6 insulation; acoustic emission; gas insulated substations; gas insulated switchgear; gas insulated transformers; partial discharges; acoustic emission signal; composite voltage; gas-insulated system; partial discharge; AC generators; Acoustic emission; Acoustic sensors; Corona; DC generators; Geographic Information Systems; Partial discharges; Power system reliability; Sulfur hexafluoride; Voltage; Acoustic emission; SF6 gas; composite voltage; gas-insulated system (GIS); partial discharge;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2005.855484
Filename
1564237
Link To Document