    Experience with AC hipot and partial discharge tests for commissioning generating station cables and switchgear

  • Author

    Gillespie, M.T.G. ; Murchie, G.B. ; Stone, G.C.

  • Author_Institution
    Ontario Hydro, Toronto, Ont., Canada
  • Volume
    4
  • Issue
    3
  • fYear
    1989
  • fDate
    9/1/1989 12:00:00 AM
  • Firstpage
    392
  • Lastpage
    396
  • Abstract
    Test equipment is described which is suitable for AC hipot and partial discharge testing of 5 and 15 kV shielded cables of lengths up to about 600 m. The equipment can be used to test 5 and 15 kV metal-clad switchgear. Ontario Hydro´s experience at two nuclear generating stations using this AC test equipment is presented. The equipment can be used to assure the integrity of cable systems (less than 600 m long) already in service. The reasons for switching to AC testing of cable systems are outlined. Practical experience shows that the partial-discharge test is very effective in identifying installation problems in cables and switchgear. A number of problems are identified with the AC tests that a DC test would have missed
  • Keywords
    cable testing; partial discharges; power cables; switchgear; switchgear testing; 5 to 15 kV; AC hipot testing; commissioning; generating station cables; nuclear generating stations; partial discharge tests; shielded cables; switchgear; AC generators; Cable insulation; Circuit testing; Partial discharges; Power cables; Power supplies; Switchgear; System testing; Test equipment; Voltage;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.43240
  • Filename
    43240