• DocumentCode
    781578
  • Title

    Study on detection for the defects of XLPE cable lines

  • Author

    Uchida, Katsumi ; Kobayashi, Shinichi ; Kawashima, Takao ; Tanaka, Hideo ; Sakuma, Susumu ; Hirotsu, Kenichi ; Inoue, Hitoshi

  • Author_Institution
    Chubu Electric Power Co. Inc., Nagoya, Japan
  • Volume
    11
  • Issue
    2
  • fYear
    1996
  • fDate
    4/1/1996 12:00:00 AM
  • Firstpage
    663
  • Lastpage
    668
  • Abstract
    This paper reports the results of a basic study of testing methods to replace the DC after laying test that is presently most frequently used as an after laying test for XLPE power cable lines. Chosen as the alternative waveforms for DC voltage were damped oscillating wave (OSW) and very-low-frequency wave (VLF) voltages. Experiments were conducted on the ability to detect various types of line defects under these voltages. It was found that these alternative waveforms are promising as after laying test voltage waveforms to replace DC and that greater defect detection ability can be achieved by combining them when conducting tests
  • Keywords
    XLPE insulation; cable laying; electric breakdown; insulation testing; power cable insulation; power cable testing; power cables; XLPE power cable lines; after laying test; damped oscillating wave voltage; defect detection; testing methods; very-low-frequency wave voltage; voltage waveforms; Acoustic testing; Cable insulation; Conducting materials; Dielectrics and electrical insulation; Electric fields; Frequency; Joining materials; Power cable insulation; Power cables; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.489320
  • Filename
    489320