• DocumentCode
    781815
  • Title

    Development of a pin-post insulator with built-in metal oxide varistors for distribution lines

  • Author

    Fujiwara, N. ; Yoneyama, T. ; Hamada, Y. ; Ishibe, S. ; Shimomura, T. ; Yamaoka, K.

  • Author_Institution
    Tokyo Electr. Power Co. Inc., Japan
  • Volume
    11
  • Issue
    2
  • fYear
    1996
  • fDate
    4/1/1996 12:00:00 AM
  • Firstpage
    824
  • Lastpage
    833
  • Abstract
    A 6.6 kV pin-post insulator, incorporating ZnO varistors, has been developed in order to reduce line faults caused by direct lightning strikes, thereby reducing and simplifying maintenance work on distribution systems. The developed insulators are interchangeable with conventional pin insulators and can withstand internal fault currents twice upon their failures. The simulated results regarding the response of the developed insulators to direct lightning strikes on an overhead ground wire agreed well with the experimental results. Simulation studies also revealed that installing the developed insulators on every two poles reduces the line-fault rate of present distribution lines in case of direct lightning strikes by 33%, while installing them on every pole reduces the rate by 97.5% or about 1/40 of the original value
  • Keywords
    arresters; current limiters; distribution networks; insulators; lightning protection; maintenance engineering; overcurrent protection; power system protection; varistors; 6.6 kV; ZnO; built-in metal oxide varistors; direct lightning strikes; distribution lines; internal fault currents; line-fault rate; maintenance; overhead ground wire; pin-post insulator; power systems; protection; simulation; Arresters; Assembly; Cable insulation; Fault currents; Lightning; Metal-insulator structures; Surge protection; Testing; Varistors; Wire; Zinc oxide;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.489340
  • Filename
    489340