DocumentCode
781894
Title
A new IEEE Application Guide for Shunt Reactor Switching
Author
Peelo, D.F. ; Ruoss, E.M.
Author_Institution
British Columbia Hydro, Vancouver, BC, Canada
Volume
11
Issue
2
fYear
1996
fDate
4/1/1996 12:00:00 AM
Firstpage
881
Lastpage
887
Abstract
The paper gives a brief overview of the content of the new IEEE Application Guide for Shunt Reactor Switching, C37.015. The interruption of shunt rector currents involves a complex interaction between the circuit breaker and the source and reactor circuits resulting in several transient overvoltage phenomena. The derivation of the overvoltage levels for the three cases of directly grounded, ungrounded and reactor grounded shunt reactors is explained. For the overvoltage calculation, the so-called chopping number concept is used. Methods of limiting the overvoltages are also discussed
Keywords
IEEE standards; circuit breakers; earthing; overvoltage protection; power system protection; power system transients; reactors (electric); C37.015; IEEE Application Guide; Shunt Reactor Switching; chopping number concept; circuit breaker; grounded shunt reactors; overvoltage levels derivation; overvoltages limiting; reactor circuits; reactor grounded shunt reactors; shunt rector currents interruption; transient overvoltage phenomena; ungrounded shunt reactors; Circuit breakers; Circuit testing; Electrical engineering; IEC standards; Inductors; Samarium; Shunt (electrical); Switching circuits; Voltage control; Writing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.489347
Filename
489347
Link To Document