DocumentCode :
782099
Title :
Electric shock and elevated EMF levels due to triplen harmonics
Author :
Tran, T.Q. ; Conrad, Larry E. ; Stallman, Brian K.
Author_Institution :
PSI Energy Inc., Plainfield, IN, USA
Volume :
11
Issue :
2
fYear :
1996
fDate :
4/1/1996 12:00:00 AM
Firstpage :
1041
Lastpage :
1049
Abstract :
The increasing use of single phase rectifiers for electric power conversion in residential applications increases harmonic load on utility systems. Many papers have analyzed the effect of these loads on power quality and equipment loadability. However, there are two more critical concerns for harmonic loads served phase to neutral on multi-grounded wye systems. Triplen harmonics, particularly the third, add in the neutral and have little diversity between loads. The higher neutral currents may cause significant problems. Neutral to earth voltages will increase near the substations which could increase stray voltage complaints. The additional neutral current on three phase lines will elevate EMF levels especially in the fringe areas. This paper provides fundamental understanding of triplen harmonic influence on stray voltage and EMF related to multi-grounded wye electric distribution systems
Keywords :
distribution networks; electric shocks; load (electric); power supply quality; power system harmonics; rectifying circuits; distribution systems; electric power conversion; electric shock; elevated EMF levels; equipment loadability; harmonic load increase; higher neutral currents; multi-grounded wye systems; neutral to earth voltages; phase to neutral loads; power quality; residential applications; single phase rectifiers; stray voltage complaints; triplen harmonics; Bridge circuits; Diodes; Earth; Electric shock; Power quality; Power system harmonics; Rectifiers; Senior members; Student members; Substations; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.489366
Filename :
489366
Link To Document :
بازگشت