DocumentCode
782910
Title
N16 Power Control System of the Livermore Pool-Type Reactor
Author
Spracklen, Howard P.
Author_Institution
University of California, Lawrence Radiation Laboratory Livermore, California
Volume
14
Issue
1
fYear
1967
Firstpage
271
Lastpage
274
Abstract
A power level indicating and control system that is independent of rod position and gamma background was developed for the Livermore Pool-Type Reactor (LPTR). This system, based on the N16 decay in the primary coolant water, avoids the errors in ion-chamber measurements caused by changes in leakage flux, related to fuel loading, fuel burnup, xenon buildup, and rod position. A scintillation detector was placed near the coolant outlet. A dual differential discriminator monitors the output and drives a counter in the control room. The numerical readout is directly in watts. The counter output provides a control signal that can override the ion-chamber control when an error exists. The system operates from 2 MW down to 2 kW under automatic control.
Keywords
Automatic control; Control systems; Coolants; Fuels; Inductors; Position measurement; Power control; Radiation detectors; Scintillation counters; Xenon;
fLanguage
English
Journal_Title
Nuclear Science, IEEE Transactions on
Publisher
ieee
ISSN
0018-9499
Type
jour
DOI
10.1109/TNS.1967.4324426
Filename
4324426
Link To Document