Title :
Observation of Prebreakdown and Breakdown Phenomena in Liquid Hydrocarbons II. Non-Uniform Field Conditions
Author :
Hebner, R.E. ; Kelley, E.F. ; Forster, E.O. ; FitzPatrick, G.J.
Author_Institution :
NBS Washington, D.C.
fDate :
4/1/1985 12:00:00 AM
Abstract :
The prebreakdown and breakdown processes have been recorded in n-hexane toluene and Marcol 70, both in a pure state and with selected impurities. The study was carried out using a point-plane geometry. A low ionization potential additive had only a small effect on the breakdown voltage or the streamer propagation speed but did significantly alter the shape of the prebreakdown streamer when the needle was positive, an anode. For a negative needle, a cathode, chemical impurities affected the breakdown voltage. The significance of these findings is discussed in detail.
Keywords :
Additives; Anodes; Cathodes; Electric breakdown; Geometry; Hydrocarbons; Impurities; Ionization; Needles; Shape;
Journal_Title :
Electrical Insulation, IEEE Transactions on
DOI :
10.1109/TEI.1985.348832