    Analysis of partial discharge pulse distribution along transformer windings using digital filtering techniques

  • Author

    Su, Qinliang

  • Author_Institution
    Dept. of Electr. & Comput. Syst. Eng., Monash Univ., Clayton, Melbourne, Vic.
  • Volume
    139
  • Issue
    5
  • fYear
    1992
  • fDate
    9/1/1992 12:00:00 AM
  • Firstpage
    402
  • Lastpage
    410
  • Abstract
    The capacitive network often used for the calculation of initial voltage distribution along a transformer winding can be in error for steep impulses. As such pulses are produced by partial discharges (PDs) the application of the concept could contribute to inaccuracies in methods developed for the location of PDs in windings. Results are presented for tests on 66 kV and 132 kV interleaved windings and a conventional 66 kV winding. It is concluded that the studies described will assist in the long-term development of more accurate electrical PD location systems
  • Keywords
    fault location; partial discharges; power transformers; transformer testing; transformer windings; 132 kV; 66 kV; capacitive network; development; digital filtering; fault location; impulses; partial discharge; power transformers; pulse distribution; transformer windings;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • Filename
    156785