• DocumentCode
    783883
  • Title

    Research on the Recovery Processes of Vacuum Gaps After 50 Hz Sinusoidal Current Zero

  • Author

    Hong-qun, Li ; Ji-mei, Wang

  • Author_Institution
    Xi´´an Jiaotong University, Department of Electrical Engineering, Xi´´an, China
  • Issue
    4
  • fYear
    1985
  • Firstpage
    745
  • Lastpage
    749
  • Abstract
    The paper reports on recovery processes of vacuum gaps after 50 Hz sinusoidal current zero. We used a vacuum interrupter with a copper button electrode, The measured recovery time was 60, 76, 100 ¿s for currents of 3, 6, and 8 kA, respectively. The theoretical analysis matches the experimental result to a certain extent. The conclusion is that the recovery time depends strongly on the arcing state and the whole heat effect of the half cycle current wave.
  • Keywords
    Breakdown voltage; Circuit testing; Current measurement; Dielectric breakdown; Electrodes; Interrupters; Probes; Switches; Switching circuits; Vacuum arcs;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/TEI.1985.348901
  • Filename
    4156859