    The authors describe the successful development of a 138 kV transition joint between high-pressure dielectric-fluid-filled cable with paper insulation and cable with extruded insulation, such as cross-linked polyethylene or ethylene propylene rubber. Such a joint must have adequate electrical and mechanical properties and contain the high-pressure dielectric fluid normally at 1400 kPa. For evaluation of the transition joint, the IEEE standard 404-1986 for laminar-to-laminar cable joints and extruded-to-extruded cable joints was considered, along with many of the specified types of tests included, such as high-voltage AC and DC, hot impulse to BIL, cyclic aging, and corona. The test results are reported
  • Keywords
    cable insulation; cable jointing; high-voltage techniques; organic insulating materials; paper; polymers; power cables; testing; 138 kV; 1400 kPa; HVAC testing; HVDC testing; IEEE standard 404-1986; corona testing; cross-linked polyethylene; cyclic aging; electrical properties; ethylene propylene rubber; extruded insulation; extruded-to-extruded cable joints; high-pressure dielectric-fluid-filled cable; hot impulse testing; laminar-to-laminar cable joints; mechanical properties; paper insulation; transition joint; Cable insulation; Cables; Circuit testing; Conducting materials; Conductors; Copper; Dielectrics and electrical insulation; Paramagnetic resonance; Solids; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.156971
  • Filename
    156971