Abstract :
The authors describe the relaying concepts of charge comparison. Charge comparison is a new transmission line protection system. It is a form of current differential relaying. Charge comparison largely resolves the traditional problems of current differential relaying of transmission lines, which are that protection is lost if a channel fails, a large channel capacity is required, and precise channel delay compensation is required. This technique is suitable for the protection of two- or three-terminal AC transmission lines, of all lengths and voltage levels, with or without series of shunt compensation, with three-hole or single-pole tripping
Keywords :
power system protection; power transmission lines; relay protection; channel delay compensation; charge comparison protection; current differential relaying; relaying; shunt compensation; single-pole tripping; three-pole tripping; three-terminal AC transmission lines; transmission lines; two-terminal lines; Channel capacity; Control systems; Delay; Digital relays; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Voltage transformers; Writing;