DocumentCode :
784486
Title :
Charge comparison protection of transmission lines-relaying concepts
Author :
Ernst, Leonard J. ; Hinman, Walter L. ; Quam, David H. ; Thorp, James S.
Author_Institution :
Dowty Control Technologies, Boonton, NJ, USA
Volume :
7
Issue :
4
fYear :
1992
fDate :
10/1/1992 12:00:00 AM
Firstpage :
1834
Lastpage :
1852
Abstract :
The authors describe the relaying concepts of charge comparison. Charge comparison is a new transmission line protection system. It is a form of current differential relaying. Charge comparison largely resolves the traditional problems of current differential relaying of transmission lines, which are that protection is lost if a channel fails, a large channel capacity is required, and precise channel delay compensation is required. This technique is suitable for the protection of two- or three-terminal AC transmission lines, of all lengths and voltage levels, with or without series of shunt compensation, with three-hole or single-pole tripping
Keywords :
power system protection; power transmission lines; relay protection; channel delay compensation; charge comparison protection; current differential relaying; relaying; shunt compensation; single-pole tripping; three-pole tripping; three-terminal AC transmission lines; transmission lines; two-terminal lines; Channel capacity; Control systems; Delay; Digital relays; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Voltage transformers; Writing;
fLanguage :
English