    Improved operation of differential protection of power transformers for internal faults

  • Author

    Liu, Pei ; Malik, O.P. ; Chen, Deshu ; Hope, G.S. ; Guo, Yong

  • Author_Institution
    Dept. of Electr. Power Eng., Huazhong Univ. of Sci. & Technol., Wuhan, China
  • Volume
    7
  • Issue
    4
  • fYear
    1992
  • fDate
    10/1/1992 12:00:00 AM
  • Firstpage
    1912
  • Lastpage
    1919
  • Abstract
    The possibility of nonoperation of second-harmonic restraint differential protection in the case of internal faults of power transformers was studied. The smaller the setting for harmonic restraint, the longer will likely be the time delay in the operation of the relay. To study this aspect, various internal faults and inrush conditions were tested on a physical model of a three-phase transformer in the laboratory. The data were analyzed by different protection algorithms. Based on the results of these studies, modified schemes for improved operation for internal faults are presented
  • Keywords
    electrical faults; harmonics; power transformers; transformer protection; differential protection; inrush conditions; internal faults; power transformers; second-harmonic restraint; Algorithm design and analysis; Capacitance; Circuit faults; Phase transformers; Power system harmonics; Power system modeling; Power system protection; Power system relaying; Power transformers; Surge protection;