DocumentCode
784571
Title
Improved operation of differential protection of power transformers for internal faults
Author
Liu, Pei ; Malik, O.P. ; Chen, Deshu ; Hope, G.S. ; Guo, Yong
Author_Institution
Dept. of Electr. Power Eng., Huazhong Univ. of Sci. & Technol., Wuhan, China
Volume
7
Issue
4
fYear
1992
fDate
10/1/1992 12:00:00 AM
Firstpage
1912
Lastpage
1919
Abstract
The possibility of nonoperation of second-harmonic restraint differential protection in the case of internal faults of power transformers was studied. The smaller the setting for harmonic restraint, the longer will likely be the time delay in the operation of the relay. To study this aspect, various internal faults and inrush conditions were tested on a physical model of a three-phase transformer in the laboratory. The data were analyzed by different protection algorithms. Based on the results of these studies, modified schemes for improved operation for internal faults are presented
Keywords
electrical faults; harmonics; power transformers; transformer protection; differential protection; inrush conditions; internal faults; power transformers; second-harmonic restraint; Algorithm design and analysis; Capacitance; Circuit faults; Phase transformers; Power system harmonics; Power system modeling; Power system protection; Power system relaying; Power transformers; Surge protection;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.156994
Filename
156994
Link To Document