DocumentCode :
784645
Title :
Development of an advanced transmission line fault location system. II. Algorithm development and simulation
Author :
Lawrence, David J. ; Cabeza, Luis Z. ; Hochberg, Lawrence T.
Author_Institution :
Power Technologies Inc., Schenectady, NY, USA
Volume :
7
Issue :
4
fYear :
1992
fDate :
10/1/1992 12:00:00 AM
Firstpage :
1972
Lastpage :
1983
Abstract :
For pt.I see ibid., vol.7, no.4, p.1963-71 (1992). The authors describe the solution techniques, system modeling considerations, and simulation studies performed as a part of the development of an advanced transmission line fault location system intended for use on the New York Power Authority´s system. The Power Authority´s Moses-Adirondack 230 kV lines were selected as a testbed for the study. A reduced model of the transmission system around the Moses-Adirondack lines was developed, and a number of electromagnetic transients program (EMTP) cases were run to establish simulated voltage and current information as fed to the fault location system. Sensitivity studies were performed to investigate the impact of various system models, hardware features, and system conditions on fault location accuracy
Keywords :
digital simulation; fault location; power system analysis computing; power transmission lines; 230 kV; EMTP; Moses-Adirondack 230 kV lines; New York Power Authority; electromagnetic transients program; sensitivity studies; simulation studies; system modeling; transmission line fault location system; Circuit faults; EMTP; Fault location; Monitoring; Power system modeling; Power transmission lines; Substations; Transducers; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.157001
Filename :
157001
Link To Document :
بازگشت