DocumentCode :
784700
Title :
Thermal stress on ZnO surge arresters in polluted conditions. II. Field test results
Author :
Vitet, S. ; Schei, A. ; Stenstrom, L. ; Lundquist, J.
Author_Institution :
Electricite de France, Clamart, France
Volume :
7
Issue :
4
fYear :
1992
fDate :
10/1/1992 12:00:00 AM
Firstpage :
2023
Lastpage :
2036
Abstract :
For pt.I see ibid., vol.7, no.4, p.2012-22 (1992). To evaluate the validity of the different laboratory test procedures, test programs were initiated to study the thermal behavior of surge arresters under natural pollution conditions. Tests were carried out on various types of surge arresters, mainly at Martigues (France) and Lista (Norway). The results obtained from the field installations are presented in areas of marine and industrial pollution, and a comparison is made with earlier laboratory test results on the basis of varistor temperature rise and accumulated charge of external leakage currents
Keywords :
leakage currents; surge protection; testing; thermal stresses; varistors; zinc compounds; France; Lista; Martigues; Norway; accumulated charge; external leakage currents; field tests; industrial pollution; marine pollution; polluted conditions; varistor temperature rise; Arresters; Environmentally friendly manufacturing techniques; Industrial pollution; Laboratories; Surges; Testing; Thermal pollution; Thermal stresses; Varistors; Zinc oxide;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.157006
Filename :
157006
Link To Document :
بازگشت