    Comparison of test circuits for high-voltage circuit breakers by numerical calculations with arc models

  • Author

    van der Sluis, L. ; Rutgers, W.R.

  • Author_Institution
    KEMA, Arnhem, Netherlands
  • Volume
    7
  • Issue
    4
  • fYear
    1992
  • fDate
    10/1/1992 12:00:00 AM
  • Firstpage
    2037
  • Lastpage
    2045
  • Abstract
    The authors use a physical arc model to compare the switching behaviors of circuit breakers in a direct and two synthetic test circuits with a computer program. It was found that not only the shape of the transient recovery voltage, but also the topology of the electrical network that supplies the transient recovery voltage after current interruption is of importance in terms of the interrupting capability of SF6 and air-blast circuit breakers
  • Keywords
    air blast circuit breakers; circuit breakers; circuit-breaking arcs; gaseous insulation; power engineering computing; sulphur compounds; switchgear testing; SF6; air-blast circuit breakers; arc models; computer program; direct test circuit; electrical network topology; high-voltage circuit breakers; interrupting capability; numerical calculations; synthetic test circuits; transient recovery voltage shape; Circuit breakers; Circuit faults; Circuit simulation; Circuit testing; Conductivity; Dielectrics; Laboratories; Protection; Switching circuits; Voltage;