  • Abstract
    An easy and swift method to evaluate, in a system of interconnected earth electrodes, earth potentials on earthing systems of medium-voltage/low-voltage (MV/LV) substations, in an event of single-line-to-earth fault inside a high-voltage/medium- voltage (HV/MV) station, is presented. The advantage of the method is the simplicity of the mathematical model for solving complex systems of any size with a sufficient accuracy for practical purposes. This paper shows the results of simulations, performed on networks with different extensions and characteristics, organized in easy-to-read graphs and tables. A comparison of these results with the values obtained according to the procedure explained in the IEC-Standard 60909-3, and a study on the accuracy of the method has been made. Moreover, some considerations on the inclusion of earth electrodes of HV/MV stations within global earthing systems are done.
  • Keywords
    earth electrodes; power system faults; power system management; power system protection; substation protection; HV network; earth potentials; earthing systems; evaluate voltages; high voltage/medium voltage station; interconnected earth electrodes; medium voltage/low voltage substations; single line to earth fault; Earthing; global earthing systems; power systems faults;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2007.915905
  • Filename
    4560040