    Effect of commutation failure on the distance protection and the countermeasures

  • Author

    Shao-feng Huang ; Hong-ming Shen ; Bin Fei ; Ou Li

  • Author_Institution
    North China Electr. Power Univ., Beijing, China
  • Volume
    9
  • Issue
    9
  • fYear
    2015
  • fDate
    6 5 2015
  • Firstpage
    838
  • Lastpage
    844
  • Abstract
    Commutation failure (CF) may be caused by AC fault in AC/DC interconnected system, and it will affect the performance of distance protection. The transient characteristic of equivalent current of power-frequency of the dc-ac inverter is first analysed by introducing the concept of quadrant. Then, the effect of CF on distance protection is studied in detail with consideration of the connection mode of distance relay. The analysis results show that both the fault position and fault resistance contribute to the effect of CF on the performance of distance protection significantly. Furthermore, a novel countermeasure based on the amplitude of second harmonic is put forward, and a concept of `successive trip´ by using the change of measured reactance is also presented. Simulation results based on PSCAD/EMTDC prove the correctness of these conclusions.
  • Keywords
    invertors; power transmission faults; power transmission protection; CF; commutation failure; dc-ac inverter; distance protection; equivalent current; fault position; fault resistance; power-frequency; second harmonic; transient characteristic;