DocumentCode :
788498
Title :
A method of defining the load impedance specification for a stable distributed power system
Author :
Wildrick, Cad M. ; Lee, Fred C. ; Cho, Bo H. ; Choi, Byungcho
Author_Institution :
AT&T Bell Labs., Mesquite, TX, USA
Volume :
10
Issue :
3
fYear :
1995
fDate :
5/1/1995 12:00:00 AM
Firstpage :
280
Lastpage :
285
Abstract :
By applying the loop gain analysis technique, a forbidden region for the polar plot of the ratio of impedances at the interface between two cascaded power subsystems is determined. A method of transforming the forbidden region into a load impedance specification for a given source impedance is developed. The method assures system stability and minimal performance degradation of the distributed power system, while allowing impedance overlap at the interface
Keywords :
Monte Carlo methods; electric impedance; load (electric); power system interconnection; power system stability; Monte Carlo analysis; distributed power system; forbidden region; impedance ratio; interconnection; interface impedance overlap; load impedance specification; loop gain analysis technique; performance degradation; polar plot; stability; Degradation; Frequency; Impedance; NASA; Power system analysis computing; Power system stability; Power systems; Sufficient conditions; Transfer functions;
fLanguage :
English
Journal_Title :
Power Electronics, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8993
Type :
jour
DOI :
10.1109/63.387992
Filename :
387992
Link To Document :
بازگشت