DocumentCode :
791802
Title :
Combining local and optimised power flow remedial measures in bulk reliability assessment
Author :
Dornellas, C. ; Schilling, M. ; Melo, A. ; Souza, J.C.S. ; Do Coutto Filho, M.B.
Volume :
150
Issue :
5
fYear :
2003
Firstpage :
629
Lastpage :
634
Abstract :
In traditional Newton-Raphson power flow algorithms, the terminal and remote bus voltages are obtained using a local control logic, i.e. reactive power and LTC taps are adjusted to meet pre-specified voltage settings. On the other hand, most of the optimal power flows (OPF) utilised in available reliability programs adopt an optimised logic for voltage control, i.e. the voltage level is optimised inside the pre-specified bounds, meaning that new settings can be calculated in order to avoid or minimise load shedding. However, in several practical situations this is not a feasible approach, due to operational constraints. Local voltage control logic is introduced into the nonlinear interior point (IP) optimal power flow of a bulk power system reliability evaluation program in order to represent actual operational practices with increased accuracy. The impact of these two voltage control logics on the reliability indices is then analysed using the new IEEE Reliability Test System (RTS-96) and an 89-bus network derived from the North/Northeastern Brazilian System (NNBS).
Keywords :
load flow; power system control; power system reliability; voltage control; 89-bus network; IEEE Reliability Test System; North/Northeastern Brazilian System; bulk power system reliability; bulk reliability assessment; load shedding minimisation; local power flow remedial measures; nonlinear interior point; optimal power flows; optimised power flow remedial measures; voltage control logic;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20030503
Filename :
1233549
Link To Document :
بازگشت