DocumentCode :
792262
Title :
Voltage stability limit of electric power systems with Generator reactive power constraints considered
Author :
Kataoka, Yoshihiko ; Shinoda, Yukio
Author_Institution :
Tokyo Electr. Power Co. Inc, Yokohama, Japan
Volume :
20
Issue :
2
fYear :
2005
fDate :
5/1/2005 12:00:00 AM
Firstpage :
951
Lastpage :
962
Abstract :
This paper investigates the smoothness of the transfer limit surface, or the loadability surface, of power systems. The reactive power output constraints of generators are taken into consideration. A new methodology employed for the investigation is based on characterizing each maximum loading point by the state of the generators (PV or PQ). Then the transfer limit surface is investigated through careful observation of nose curves. In those special cases with only one constraint, the transfer limit surface is smooth. However, in the more general case of multiple constraints, the transfer limit surface is nonsmooth. These properties have been confirmed in a numerical example using a system with two constraints and three load parameters.
Keywords :
electric generators; power system stability; reactive power; electric power system; loadability surface; reactive power constraint; transfer limit surface; voltage stability limit; Bifurcation; Character generation; Nose; Power generation; Power system modeling; Power system reliability; Power system stability; Reactive power; Steady-state; Voltage; Bifurcation set; electric power system; generator reactive power limits; inequality constraints; static model; transfer limit surface; voltage stability;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2005.846080
Filename :
1425593
Link To Document :
بازگشت