Loss-of-Excitation Protection for Synchronous Generators on Isolated Systems
Author :
Pierre, Conrad R.St.
Author_Institution :
General Electric Company, ISPEO, Building 6-303, 1 River Road, Schenectady, NY 12345.
Issue :
1
fYear :
1985
Firstpage :
81
Lastpage :
98
Abstract :
Loss-of-field relays operating on an impedance-measuring principle provide an important part of the protection of a synchronous generator by minimizing possible damage to the machine and low voltages detrimental to system operation. These relays require an external source of reactive power, such as a utility tie or other in-plant generators, to insure proper operation on loss of generator field. In a multigenerator isolated system, the reactive current provided by the remaining generators may not be sufficiently large to allow proper operation of the loss-of-field relays on the generator in question. Some guidelines are provided as to the relative size of synchronous generators needed to insure proper operation of the impedance type loss-of-field relays.
Keywords :
Guidelines; Impedance; Low voltage; Power generation; Power system protection; Power system relaying; Protective relaying; Reactive power; Relays; Synchronous generators;