DocumentCode :
795524
Title :
The Analysis of Current Transformer Transient Response and Its Effect on Current Relay Performance
Author :
Wu, Alex Y.
Author_Institution :
Simons-Eastern Company, P.O. Box 1286, Atlanta, GA 30301.
Issue :
3
fYear :
1985
fDate :
5/1/1985 12:00:00 AM
Firstpage :
793
Lastpage :
802
Abstract :
The current transformer transient response will affect the performance of protective relaying. Various factors are examined which will influence current transformer transient response. Formulas are developed for estimating the time to saturation and the time to desaturation of a current transformer during a fully saturated condition. Three current transformer and relaying arrangements are also presented for minimizing the impact of current transformer transient response.
Keywords :
AC generators; Current transformers; Performance analysis; Power system harmonics; Power system relaying; Protective relaying; Relays; Short circuit currents; Transient response; Voltage;