• DocumentCode
    795727
  • Title

    Parallel Operation of Magnetic Frequency Triplers

  • Author

    Suzuki, H. ; Tadokoro, M.

  • Author_Institution
    The Tokyo Electric Power Co. Inc.
  • Volume
    5
  • Issue
    8
  • fYear
    1990
  • Firstpage
    640
  • Lastpage
    647
  • Abstract
    Magnetic frequency triplers provide high reliability and a good output waveform, and therefore have been widely. used This paper reports experiments and analyses of the parallel running of two frequency tripler units to increase the capacity of the device. Parallel running creates a problem involving effective loads, in which the frequency tripler whose self-impedance has a proportionately smaller resistance component is the first to be overloaded. The authors analyzed the parallel running characteristics using the harmonic balance method. The relationship between the circulating power and the device circuit constants was clarified, and parallel running conditions which increase the effective load were determined.
  • Keywords
    Capacitance; Circuits; Electrical equipment industry; Electricity supply industry; Electronic equipment manufacture; Frequency conversion; Inductors; Magnetic analysis; Magnetics Society; Power conversion;
  • fLanguage
    English
  • Journal_Title
    Magnetics in Japan, IEEE Translation Journal on
  • Publisher
    ieee
  • ISSN
    0882-4959
  • Type

    jour

  • DOI
    10.1109/TJMJ.1990.4564313
  • Filename
    4564313