DocumentCode
797023
Title
An adaptive scheme to prevent undesirable distance protection operation during voltage instability
Author
Jonsson, Mattias ; Daalder, Jaap E.
Author_Institution
Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Gothenburg, Sweden
Volume
18
Issue
4
fYear
2003
Firstpage
1174
Lastpage
1180
Abstract
An adaptive algorithm to prevent undesirable distance protection operations during voltage instability is proposed. The algorithm is based on mathematical logic blocks and uses the rate of change of voltage as an additional relay criteria to increase the relay security with respect to voltage instability. Studies are based on simulations using two different test systems; a 15-bus system developed by the authors and the Nordic32 system. The investigation shows that undesirable zone 3 distance relay operations can be the difference between a blackout and a recovering system during voltage instability. However, simulations have shown that the adaptive algorithm may save the system from a collapse. Although the algorithm prevents mal-trips due to voltage instability, the reach of the distance relay will not be restricted.
Keywords
power system dynamic stability; power system protection; power system relaying; power system simulation; relay protection; 15-bus system; Nordic32 system; adaptive relaying; adaptive scheme; additional relay criteria; blackout; mathematical logic blocks; recovering system; relay security; remote back-up; simulation; undesirable distance protection operation prevention; undesirable zone 3 distance relay operations; voltage instability; Adaptive algorithm; Circuits; Logic; Power system protection; Power system relaying; Power system security; Power system stability; Power transmission lines; Protective relaying; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2003.817501
Filename
1234666
Link To Document