    Application of OPPL semi-synthetic paper to EHV oil-filled cables

  • Author

    Kaminaga, K. ; Komaba, T. ; Kanai, K. ; Iwata, Z. ; Ichiyanagi, N. ; Kasuya, M. ; Nakayama, K. ; Asada, Y.

  • Author_Institution
    Tokyo Electric Power Co. Inc., Japan
  • Volume
    27
  • Issue
    3
  • fYear
    1992
  • fDate
    6/1/1992 12:00:00 AM
  • Firstpage
    566
  • Lastpage
    571
  • Abstract
    Biaxially oriented polypropylene laminated paper (OPPL), composed of biaxially oriented polypropylene and kraft paper, has superior electrical and mechanical properties. 275 kV OPPL oil-filled cable has already been installed and OPPL POF (pipe type oil filled) cable is under development. By using OPPL, the insulation thickness can be reduced by 3 mm. Therefore, the conductor size of the POF cable can be increased without any change of cable core diameter, which makes it possible to increase the transmission capacity of the POF cable within a limited pipe size
  • Keywords
    cable insulation; composite insulating materials; high-voltage engineering; insulating oils; laminates; paper; polymer films; power cables; EHV oil-filled cables; insulation thickness; kraft paper; oriented polypropylene laminated paper; pipe type oil filled; semi-synthetic paper; transmission capacity; Cable insulation; Dielectric losses; Dielectrics and electrical insulation; Electric resistance; Mechanical factors; Oil filled cables; Oil insulation; Petroleum; Plastics; Power cables;