• DocumentCode
    797057
  • Title

    New techniques for monitoring the insulation quality of in-service HV apparatus

  • Author

    Allan, D. ; Blundell, M. ; Boyd, K. ; Hinde, D.

  • Volume
    27
  • Issue
    3
  • fYear
    1992
  • fDate
    6/1/1992 12:00:00 AM
  • Firstpage
    578
  • Lastpage
    585
  • Abstract
    New online monitoring techniques have been developed for use on HV systems. An online testing device was developed to measure partial discharge and dielectric loss angle (DLA) of in-service HV instrument transformers and is used as a fast screening device. A continuous DLA monitor for in-service transformer bushings and current transformers has also been developed and installed at a 132 kV substation. These techniques considerably enhance HV plant maintenance programs and have a significant impact on future plant monitoring strategies
  • Keywords
    current transformers; dielectric measurement; high-voltage engineering; instrument transformers; insulation testing; loss-angle measurement; partial discharges; transformer insulation; transformer substations; transformer testing; 132 kV; HV instrument transformers; current transformers; dielectric loss angle; fast screening device; in-service HV apparatus; insulation quality; online monitoring techniques; online testing device; partial discharge; plant maintenance programs; transformer bushings; Current transformers; Dielectric loss measurement; Dielectric measurements; Dielectrics and electrical insulation; Instrument transformers; Loss measurement; Monitoring; Partial discharge measurement; Power transformer insulation; Testing;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/14.142722
  • Filename
    142722