Title :
Reliability Considerations in Systems Applications of Uninterruptible Power Supplies
Author :
Heising, Charles R. ; Johnston, James F., Jr.
Author_Institution :
Power Transmission Division, General Electric Company, Philadelphia, Pa. 19142.
fDate :
3/1/1972 12:00:00 AM
Abstract :
A redundant static inverter is applied as an uninterruptible power supply (UPS). A reliability analysis is presented showing that the introduction of a static bypass transfer switch brings about a reliability improvement of 8.5 to 1 in the mean time between failure (MTBF). This gives MTBF greater than 600 000 h. The static bypass transfer switch provides a synchronized automatic transfer in less than 1 ms from the UPS to the normal ac input power source upon a failure of the UPS.
Keywords :
Batteries; Failure analysis; Interrupters; Inverters; Oscillators; Power supplies; Power system reliability; Rectifiers; Switches; Uninterruptible power systems;