Title :
Proposed standards for frequency conversion factors of transformer performance parameters
Author :
Girgis, Ramsis S. ; TeNyenhuis, Ed G. ; Beaster, Barry
Author_Institution :
ABB Power T&D Co. Inc., St. Louis, MO, USA
Abstract :
This paper presents the development of appropriate frequency conversion factors for performance parameters of transformers. These factors are needed in order to allow manufacturers to convert measured values from 60 to 50 Hz and vice versa. Conversion factors are necessary when equipment at a manufacturer´s test facility allows direct measurement at one frequency and not the other. These factors are developed in this paper for no load loss, exciting current, load loss, and noise level using both analytical and actual tested data. The measured data, provided by several manufacturers, were used to confirm the theoretical results. This paper can be used as a basis for proposing standard frequency conversion factors in the IEEE/ANSI and IEC test standards for power and distribution transformers. Such a standard makes it possible for manufacturers to use the same frequency conversion factors, and hence, have a more uniform accuracy of the reported test data at both 50 and 60 Hz.
Keywords :
ANSI standards; IEC standards; IEEE standards; acoustic noise; eddy current losses; power transformer testing; 50 Hz; 60 Hz; IEC standard; IEEE ANSI standard; distribution transformers; exciting current; frequency conversion factors; load loss; noise level; performance parameters; power transformers; test standards; ANSI standards; Frequency conversion; Frequency measurement; IEC standards; Magnetic materials; Manufacturing; Noise level; Noise measurement; Power transformers; Testing;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2003.817737