• DocumentCode
    797200
  • Title

    Prediction of hottest spot temperature (HST) in power and station transformers

  • Author

    Pradhan, M.K. ; Ramu, T.S.

  • Author_Institution
    Dept. of High Voltage Eng., Indian Inst. of Sci., Bangalore, India
  • Volume
    18
  • Issue
    4
  • fYear
    2003
  • Firstpage
    1275
  • Lastpage
    1283
  • Abstract
    The degradation of electrical insulation in transformers is more often due to thermal stress. In this paper, the authors attempted to work out a method of assessing the magnitude of temperature and the hottest region in the body of a large transformer with a reasonable degree of accuracy. A theoretical model has been developed based on the boundary value problem of heat conduction in transformer winding using finite integral transform techniques. The model requires, in addition to electrical parameters of the transformer, information on the actual design data. The authors believe that this model predicts HST with precision and also indicates a possibility of online data acquisition.
  • Keywords
    Fourier transforms; boundary-value problems; heat conduction; impregnated insulation; paper; power transformer insulation; temperature distribution; transformer oil; IEEE loading guide; boundary value problem; finite integral transform; heat conduction; heat transfer; hottest region; oil impregnated paper; power transformers; prediction accuracy; temperature rise; transformer winding; Boundary value problems; Data acquisition; Dielectrics and electrical insulation; Integral equations; Power transformer insulation; Predictive models; Temperature; Thermal degradation; Thermal stresses; Windings;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2003.817739
  • Filename
    1234681