DocumentCode :
797220
Title :
Review of time-domain polarization measurements for assessing insulation condition in aged transformers
Author :
Saha, Tapan Kumar
Author_Institution :
Sch. of Inf. Technol. & Electr. Eng., Univ. of Queensland, Qld., Australia
Volume :
18
Issue :
4
fYear :
2003
Firstpage :
1293
Lastpage :
1301
Abstract :
This paper presents a review of the time-domain polarization measurement techniques for the condition assessment of aged transformer insulation. The polarization process is first described with appropriate dielectric response theories and then commonly used polarization methods are described with special emphasis on the most widely used "return voltage" (RV) measurement. Most recent emphasis has been directed to techniques of determining moisture content of insulation indirectly by measuring RV parameters. The major difficulty still lies with the accurate interpretation of return voltage results. This paper investigates different thoughts regarding the interpretation of RV results for different moisture and ageing conditions. Other time domain polarization measurement techniques and their results are also presented in this paper.
Keywords :
ageing; dielectric polarisation; electric current measurement; moisture; power transformer insulation; time-domain analysis; voltage measurement; ageing conditions; condition assessment; depolarization currents; dielectric response; moisture; polarization currents; power transformers; return voltage measurement; time-domain polarization measurements; transformers insulation; Aging; Current measurement; Dielectric measurements; Dielectrics and electrical insulation; Electrical resistance measurement; Moisture; Polarization; Power transformer insulation; Time domain analysis; Voltage measurement;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2003.817741