DocumentCode :
797292
Title :
Transient behavior of load transformer during subcycle bus transfer
Author :
Mokhtari, Hossein ; Iravani, M. Reza ; Dewan, Shashi B.
Author_Institution :
Dept. of Electr. Eng., Sharif Univ. of Technol., Tehran, Iran
Volume :
18
Issue :
4
fYear :
2003
Firstpage :
1342
Lastpage :
1349
Abstract :
Fast (subcycle) bus transfer by means of a static transfer switch (STS) requires short time intervals for the detection and transfer process. Due to these time intervals, the load transformer is subjected to a transient process which can be accompanied by large transient current components through the transformer. The transient current, in turn, can cause voltage sag at the load terminal. The STS control logic must be able to distinguish such a voltage sag from those due to the supply disturbances and not disconnected from the load. This paper provides simplified analytical expressions to predict F of the load transformer which can be used to estimate the corresponding voltage sag. The PSCAD/EMTDC-based digital simulation of the actual nonlinear system is also carried out to substantiate the validity of the analytical expressions.
Keywords :
load (electric); power supply quality; power system transients; power transformers; switchgear; PSCAD/EMTDC-based simulation; load transformer; peak transient flux estimation; power quality; sensitive loads; static transfer switch; subcycle bus transfer; three-phase voltage sag; transient current; utility feeders; Circuit faults; Digital simulation; Fault detection; Logic; PSCAD; Sociotechnical systems; Switches; Transient analysis; Voltage control; Voltage fluctuations;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2003.817750
Filename :
1234690