• DocumentCode
    797354
  • Title

    Voltage recovery after unbalanced and balanced voltage dips in three-phase systems

  • Author

    Bollen, Math H J

  • Author_Institution
    Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Gothenburg, Sweden
  • Volume
    18
  • Issue
    4
  • fYear
    2003
  • Firstpage
    1376
  • Lastpage
    1381
  • Abstract
    This paper studies the recovery of the voltage after a voltage dip due to a fault in a three-phase system. The instant of voltage recovery corresponds to the instant of fault clearing. For single-phase and phase-to-phase faults, a single point-on-wave of voltage recovery can be defined. For two-phase-to-ground and three-phase faults, the recovery takes place in two or three steps. The voltage recovery is described in a systematic way by using a classification of three-phase unbalanced voltage dips. The voltage recovery needs to be modeled correctly for studies of equipment immunity against voltage dips.
  • Keywords
    power distribution; power supply quality; power system faults; power transmission; equipment immunity; power distribution; power quality; power transmission; solidly-grounded systems; three-phase faults; three-phase system; two-phase-to-ground faults; unbalanced voltage dips; voltage recovery; voltage sags; Circuit faults; Electronics packaging; Power quality; Power system faults; Power system modeling; Power system simulation; Power transmission; Shape measurement; Surges; Voltage fluctuations;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2003.817725
  • Filename
    1234695