Title :
Selectivity of damped AC (DAC) and VLF voltages in after-laying tests of extruded MV cable systems
Author :
Oyegoke, Bolarin ; Hyvonen, Petri ; Aro, Martti ; Gao, Ning
Author_Institution :
High Voltage Inst., Helsinki Univ. of Technol., Finland
Abstract :
The purpose of HV after-laying tests on cable systems on-site is to check the quality of installation. The test on extruded MV cable systems is usually a voltage test. However, in order to enhance the quality of after installation many researchers have proposed performance of diagnosis tests such as detection, location and identification of partial discharges (PD) and tan δ measurements. Damped AC voltage (DAC) also called oscillating voltage waves (OVW) is used for PD measurement in after-laying tests of new cables and in diagnostic test of old cables. Continuous AC voltage of very low frequency (VLF) is used for withstand voltage tests as well as for diagnostic tests with PD and tan δ measurements. Review on the DAC and VLF tests to detect defects during on-site after-laying tests of extruded MV cable systems is presented. Selectivity of DAC and VLF voltages in after-laying testing depends on different test parameters. PD process depends on type and frequency of the test voltage and hence, the breakdown voltage is different. The withstand voltage of XLPE cable insulation decreases linearly with increasing frequency in log scale. Experimental studies with artificial XLPE cable model indicate that detection of defects with DAC or VLF voltage can be done at a lower voltage than with DC. DAC voltage is sensitive in detecting defects that cause a breakdown due to void discharge, while VLF is sensitive in detecting defects that cause breakdown directly led by inception of electrical trees.
Keywords :
XLPE insulation; insulation testing; partial discharge measurement; power cable insulation; power cable testing; trees (electrical); voids (solid); HV after-laying tests; PD measurement; VLF voltages; XLPE cable insulation; breakdown voltage; damped AC voltages; diagnosis tests; electrical trees; extruded MV cable systems; oscillating voltage waves; partial discharges detection; partial discharges identification; partial discharges location; tan d measurements; void discharge; withstand voltage tests; Breakdown voltage; Cable insulation; Frequency; Insulation testing; Low voltage; Partial discharges; Pollution measurement; Power cables; Power measurement; System testing;
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
DOI :
10.1109/TDEI.2003.1237335