Title :
Review of modern diagnostic techniques for assessing insulation condition in aged transformers
Author_Institution :
Sch. of Inf. Technol. & Electr. Eng., Queensland Univ., Brisbane, Qld., Australia
Abstract :
Cellulosic paper and oil insulation in a transformer degrade at higher operating temperatures. Degradation is accelerated in the presence of oxygen and moisture. Power transformers being expensive items need to be carefully monitored throughout their operation. Well established time-based maintenance and conservative replacement planning is not feasible in a current market driven electricity industry. Condition based maintenance and online monitoring are now gaining importance. Currently there are varieties of chemical and electrical diagnostic techniques available for insulation condition monitoring of power transformers. This paper presents a description of commonly used chemical diagnostics techniques along with their interpretation schemes. A number of new chemical techniques are also described in this paper. A number of electrical diagnostic techniques have gained exceptional importance to the utility professionals. Among these techniques polarisation/depolarisation current measurement, return voltage measurement and frequency domain dielectric spectroscopy at low frequencies are the most widely used. This paper describes analyses and interpretation of these techniques for transformer insulation condition assessment.
Keywords :
chemical analysis; chemical variables measurement; condition monitoring; dielectric measurement; electric current measurement; frequency-domain analysis; insulation testing; paper; polarisation; polymerisation; power transformer insulation; power transformer testing; transformer oil; voltage measurement; aged transformers; cellulosic paper insulation; chemical diagnostics techniques; condition based maintenance; depolarisation current measurement; diagnostic techniques; dissolved gas analysis; frequency domain dielectric spectroscopy; furan analysis; insulation condition assessment; insulation condition monitoring; insulation degradation; liquid chromatography; moisture analysis; oil insulation; online monitoring; polarisation current measurement; polymerization; power transformers; return voltage measurement; transformer insulation condition assessment; Acceleration; Aging; Chemicals; Condition monitoring; Degradation; Dielectrics and electrical insulation; Oil insulation; Power transformer insulation; Power transformers; Temperature;
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
DOI :
10.1109/TDEI.2003.1237337