• DocumentCode
    812050
  • Title

    Active power filters using resonant pole inverters

  • Author

    Acharya, Beena ; Divan, Deepakraj M. ; Gascoigne, Randal W.

  • Author_Institution
    EML Res. Inc., Northboro, MA, USA
  • Volume
    28
  • Issue
    6
  • fYear
    1992
  • Firstpage
    1269
  • Lastpage
    1276
  • Abstract
    The use of a new soft switching inverter topology, the resonant pole inverter (RPI), for harmonic compensator realization, is proposed. Using resonant transitions to minimize switching losses, the topology is suitable for use with GTOs and other gate turn-off devices. Switching frequencies on the order of 10-20 kHz at multikilowatt power levels are feasible. A current-mode modulation strategy is proposed and is seen to realize good spectral characteristics. Extensive simulation and experimental results of a 10 kVA GTO resonant pole inverter switching between 10 and 20 kHz confirm the validity of the approach
  • Keywords
    active filters; compensation; harmonics; invertors; switching; thyristor applications; 10 kVA; 10 to 20 kHz; GTO resonant pole inverter; active power filters; current-mode modulation; harmonic compensator realization; soft switching inverter topology; spectral characteristics; switching losses; Active filters; Current control; Economic indicators; Industry Applications Society; Power harmonic filters; Power system harmonics; Pulse width modulation inverters; Resonance; Switching frequency; Topology;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.175277
  • Filename
    175277