    Insulation recovery time after fault arc interruption for rapid auto-reclosing on UHV (1000 kV class) transmission lines

  • Author

    Goda, Yutaka ; Matsuda, Shoji ; Inaba, Tsuginori ; Ozaki, Yuzo

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Yokosuka, Japan
  • Volume
    10
  • Issue
    2
  • fYear
    1995
  • fDate
    4/1/1995 12:00:00 AM
  • Firstpage
    1060
  • Lastpage
    1065
  • Abstract
    The insulation recovery time after arc interruption must be known in order to select an adequate reclosing dead time of rapid auto-reclosing on transmission lines. The flashover probability of the insulation recovery voltage obtained from the insulation recovery tests using full size insulator assemblies was calculated. The insulation recovery time at the fault point for rapid auto-reclosing on UHV (1000 kV class) transmission lines was estimated
  • Keywords
    arcs (electric); electrical faults; flashover; insulation; insulators; power system restoration; power transmission lines; probability; 1000 kV; UHV transmission lines; fault arc interruption; flashover probability; insulation recovery time; insulator assemblies; rapid auto-reclosing; reclosing dead time selection; Arc discharges; Assembly; Circuit faults; Circuit testing; Dielectrics and electrical insulation; Flashover; Insulation testing; Power system faults; Power transmission lines; Voltage;