DocumentCode
812649
Title
Further studies of anomalous phenomena in dielectric-loss measurements-transformer bushings model
Author
Levi, Raka ; Manifase, Stan
Author_Institution
Doble Eng. Co., Watertown, MA, USA
Volume
10
Issue
2
fYear
1995
fDate
4/1/1995 12:00:00 AM
Firstpage
889
Lastpage
895
Abstract
The results of AC dielectric loss measurements on bushings mounted in certain three-phase transformers, if not performed in accordance with the prescribed procedure, can deviate significantly from the correct values. An investigation of the incorrect procedure has shown that the capacitive coupling between adjacent windings and the lower portion of the bushings influenced the results such that dielectric losses were elevated to several times their normal values. Experience has shown that bushing test results on all three phases form a pattern in cases where this phenomena is evident. Results of investigative field measurements showing this phenomena are presented, and an explanation of its origin is given
Keywords
bushings; dielectric loss measurement; dielectric losses; electric breakdown; insulation testing; insulator testing; measurement errors; power transformer insulation; power transformer testing; transformer windings; AC dielectric loss measurements; adjacent windings; anomalous phenomena; capacitive coupling; field measurements; three-phase; transformer bushings; Circuit testing; Dielectric losses; Dielectric measurements; Dielectrics and electrical insulation; Insulation testing; Insulators; Performance evaluation; Pollution measurement; Power transformer insulation; Windings;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.400841
Filename
400841
Link To Document