    Further studies of anomalous phenomena in dielectric-loss measurements-transformer bushings model

  • Author

    Levi, Raka ; Manifase, Stan

  • Author_Institution
    Doble Eng. Co., Watertown, MA, USA
  • Volume
    10
  • Issue
    2
  • fYear
    1995
  • fDate
    4/1/1995 12:00:00 AM
  • Firstpage
    889
  • Lastpage
    895
  • Abstract
    The results of AC dielectric loss measurements on bushings mounted in certain three-phase transformers, if not performed in accordance with the prescribed procedure, can deviate significantly from the correct values. An investigation of the incorrect procedure has shown that the capacitive coupling between adjacent windings and the lower portion of the bushings influenced the results such that dielectric losses were elevated to several times their normal values. Experience has shown that bushing test results on all three phases form a pattern in cases where this phenomena is evident. Results of investigative field measurements showing this phenomena are presented, and an explanation of its origin is given
  • Keywords
    bushings; dielectric loss measurement; dielectric losses; electric breakdown; insulation testing; insulator testing; measurement errors; power transformer insulation; power transformer testing; transformer windings; AC dielectric loss measurements; adjacent windings; anomalous phenomena; capacitive coupling; field measurements; three-phase; transformer bushings; Circuit testing; Dielectric losses; Dielectric measurements; Dielectrics and electrical insulation; Insulation testing; Insulators; Performance evaluation; Pollution measurement; Power transformer insulation; Windings;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.400841
  • Filename
    400841