DocumentCode
813434
Title
A study on probabilistic assessment of contamination flashover of high voltage insulator
Author
Naito, K. ; Mizuno, Y. ; Naganawa, W.
Author_Institution
Nagoya Inst. of Technol., Japan
Volume
10
Issue
3
fYear
1995
fDate
7/1/1995 12:00:00 AM
Firstpage
1378
Lastpage
1384
Abstract
Insulation design against insulator contamination has been made so far by using the traditional deterministic method. In this method, the maximum contamination severity is first assumed. Then, a certain margin is counted between the withstand voltage obtained from actual tests and the target operating voltage. However, both contamination severity and the withstand voltage are probabilistic variables. In the present paper, as a first step in this probabilistic approach, a risk-of-failure study of 800 kV transmission line insulation was made by treating contamination severity and degree of wetting as probabilistic variables
Keywords
electric breakdown; electric strength; failure analysis; flashover; insulator contamination; power overhead lines; power transmission lines; probability; 800 kV; contamination flashover; contamination severity; insulator contamination; probabilistic assessment; risk-of-failure; transmission line insulation; withstand voltage; Contamination; Flashover; Insulation; Power system dynamics; Power system reliability; Power transmission lines; Probability; Testing; Transmission line measurements; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.400919
Filename
400919
Link To Document